Viessmann · Boiler troubleshooting

Connecting a 24 VAC thermostat through a switching relay

Vitodens 200-W B2HB

What is going on

Use a switching relay with a normally open, potential-free dry contact (T-T). Wire the contact to input DE1, DE2 or DE3 on extension module EA1 in the boiler electrical junction box. Power the relay and thermostat as the manufacturer instructs. When the thermostat contact closes, burner operation is load-dependent and the supply water heats to the value in coding address 9b (General group). The supply temperature is still limited by the electronic supply temperature maximum. Live contacts cause short circuits or phase failure, so the connection must be potential-free. For thermostat-only room control, the standard and reduced room temperature set points can be set to 37 ºF (3 ºC) to reduce cycling. Example relays named in the manual are Taco SR501 and Honeywell RA889A-1001, both field supplied.

Check in this order

  1. Connect the normally open dry contact (T-T) of the switching relay to DE1, DE2 or DE3 on EA1.
  2. Connect the relay to the thermostat and power supply per manufacturer instructions.
  3. Set coding 3A, 3B or 3C in the General group to 2.
  4. Set coding 9b to the required maximum supply water temperature.
  5. Keep the contact potential-free.

Applies to: Vitodens 200-W B2HB 19 to 35, 68 to 125

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HB 19 to 35, 68 to 125 Installation Instructions, p. 51. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.