Weil-McLain · Boiler troubleshooting

Measure natural gas input

ECO Tec Series 3

What is going on

Confirm the calculated input is close to the rating label.

Check in this order

  1. Operate the boiler 10 minutes and turn off other gas appliances.
  2. At the natural gas meter, time how many seconds one cubic foot of gas takes.
  3. Calculate input 3600 x 1000 divided by the number of seconds, giving Btuh.
  4. Confirm the Btuh result approximately matches the input rating on the boiler rating label.

Applies to: ECO Tec Series 3 80/110/150/199

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 135. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.