Beckett · Boiler troubleshooting

NX burner: annual service checklist

Beckett NX

What is going on

Yearly service list for the NX. Power off before working on it.

Likely causes

  • Annual service due
  • Dusty or dirty room (service more often)

Check in this order

  1. Turn off power to the burner. Remove the cover (four thumb screws).
  2. Replace the oil line filter cartridge. Clean the pump strainer if it has one. Check all oil fittings for leaks and the lines for water or sludge.
  3. Pull the nozzle line (disconnect connector tube, release igniter clips, open rear door, loosen splined nut). Replace the nozzle; hold the adapter with a 3/4 in. wrench, tighten with 5/8 in. Do not over-tighten.
  4. Clean and check electrodes; replace if cracked, chipped or rounded tips. Check electrode tip settings and igniter spring contacts.
  5. Clean the cad cell lens. Make sure the low firing rate baffle is in place if the setup needs it.
  6. Clean the blower wheel, air inlet, air guide, retention head, throttle cup and throttle ring. Clean the throttle cup sight windows gently.
  7. Check gaskets, motor amps (not above nameplate) and wiring.
  8. Check pump pressure and cutoff, primary control lockout timing and ignition.
  9. Clean the boiler flue passages, flue pipe and chimney. Replace corroded pipe.
  10. Set combustion with an analyzer and record the readings.

Applies to: Beckett NX burner with GeniSys 7505 primary control on Weil-McLain Ultra Oil UO-3, UO-4, UO-5 (CV and DV)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Beckett NX Burner Manual for Weil-McLain Ultra Oil boilers (W-M 550-141-996/0321), Trained service technician's regular maintenance p.16-18. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.