Viessmann · Boiler troubleshooting
Combustion faults caused by pulsation
What is going on
Pulsating combustion can come from gas flow, air balance, condensate or flue problems.
Likely causes
- Excessive gas throughput
- Insufficient or excessive combustion air
- Condensate drain in the flue system blocked
- Flue outlet not installed correctly
- Insufficient draught in the flue system
Check in this order
- Adjust the gas throughput to match the rated boiler heating output.
- Correct the air settings.
- Check the condensate drain.
- Check the flue outlet and flue system.
- Check combustion in the installation room.
- Check the flue system for adequate draught.
Applies to: Vitocrossal 200 CI2
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CI2 Service Instructions, p. 75. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.