Navien · Boiler troubleshooting

Condensate drain disposal and connection

NCB700

What is going on

Condensate is acidic (pH 3-5). Follow local codes. Draining into a laundry tub is recommended because detergent neutralizes the acid. Options: direct to an external drain, through a neutralizer then to drain, from a higher boiler into a laundry tub, or via a condensate pump into a laundry tub. A pump is used when the drain run is long or the boiler sits lower than the tub.

Check in this order

  1. Choose a disposal option that meets local codes.
  2. Connect a drain line to the 1/2 in NPT fitting at the bottom of the boiler.
  3. Use only corrosion-resistant drain line such as PVC or CPVC.
  4. Do not reduce the fitting or drain line below 1/2 in.
  5. If using a pump, make sure it handles at least 2 GPH per boiler in the system.
  6. If not using a pump, pitch the drain line down at least 1/4 in per foot.
  7. Where the grade is insufficient, install a drainage pump rated for boiler condensate.
  8. Fill the condensate trap with water after installing the drain pipe.
  9. Do not cap or plug the condensate line and keep it from freezing.
  10. Never let people or animals drink condensate.

Applies to: NCB700 condensate drain

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NCB700 installation and operation manual, p. 25-26. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.