Viessmann · Boiler troubleshooting
Check the burner flue gas flapper
What is going on
Inspect the flapper and gasket for dirt and damage.
Check in this order
- Remove the three screws and fan A.
- Remove burner flue gas flapper B.
- Check the flapper and gasket for dirt and damage. Replace as needed.
- Refit the flapper, then refit fan A with three screws torqued to 2.2 lb.ft (3.0 Nm).
Applies to: Vitodens 222-F B2TB 19, 35, 68, 125
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 222-F B2TB service instructions, p. 23. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.