External high limit setpoint and multi-temperature systems

ECO Tec Series 3

What is going on

Some jurisdictions require an added manual reset high limit. The control high limit shuts the boiler at 195 F or lower if set lower. The external manual reset limit must not be set above 200 F in the piping between boiler and isolation valve. Low temperature circuits such as radiant slab or PEX need their own limit controls wired to the external limit circuit. A combi in a low temperature system is multi-temperature.

Check in this order

  1. Confirm local code requirement for an external high temperature limit.
  2. Install a manual reset high limit set no higher than 200 F, in piping between boiler and isolation valve.
  3. Set the control boiler limit at least 20 F below the external manual reset limit (example: control no higher than 180 F for a 200 F external limit).
  4. Protect low temperature circuits with limit controls wired to the control external limit circuit terminals.
  5. Wire the limit controls per the field wiring instructions starting on page 65.

Applies to: All ECO Tec Series 3 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec Series 3 Boiler Manual, p. 47. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.