Weil-McLain · Boiler troubleshooting
External high limit setpoint and multi-temperature systems
What is going on
Some jurisdictions require an added manual reset high limit. The control high limit shuts the boiler at 195 F or lower if set lower. The external manual reset limit must not be set above 200 F in the piping between boiler and isolation valve. Low temperature circuits such as radiant slab or PEX need their own limit controls wired to the external limit circuit. A combi in a low temperature system is multi-temperature.
Check in this order
- Confirm local code requirement for an external high temperature limit.
- Install a manual reset high limit set no higher than 200 F, in piping between boiler and isolation valve.
- Set the control boiler limit at least 20 F below the external manual reset limit (example: control no higher than 180 F for a 200 F external limit).
- Protect low temperature circuits with limit controls wired to the control external limit circuit terminals.
- Wire the limit controls per the field wiring instructions starting on page 65.
Applies to: All ECO Tec Series 3 boilers
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec Series 3 Boiler Manual, p. 47. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.