Viessmann · Boiler troubleshooting

Heating status is off

Vitotron 100 VLN2

What is going on

The boiler is not receiving a heat call or the control board has failed.

Likely causes

  • No thermostat connection
  • Thermostat not calling for heat or room is already above set point
  • Control board failure

Check in this order

  1. Make sure the thermostat is calling for heat and the room is below the thermostat set point.
  2. Verify the connections on the thermostat.
  3. Check the glass fuse on the control panel (6.3 x 32 mm, 2 A).

Applies to: Vitotron 100 VLN2

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotron 100 installation and service instructions, p. 18. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.