System layout 2: underfloor circuit with mixing valve and system separation
What is going on
Low-temperature underfloor heating isolated by a plate heat exchanger, with DHW production. Required where non-oxygen-barrier tubing is used.
Check in this order
- Install a plate heat exchanger for system separation.
- Use corrosion-resistant materials on the secondary side of the heat exchanger.
- Size the field-supplied pump P carefully using the boiler supply head pressure drop on page 18.
- Connect the accessory kit for the mixing valve circuit and the mixing valve temperature sensor.
- Set the DHW recirculation pump function per coding address 53.
Applies to: Vitocrossal 300 CU3A, system layout 2
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitocrossal 300 CU3A installation manual, p. 45. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.