Weil-McLain · Boiler troubleshooting
Check temperature sensors
What is going on
Sensors (flue, outdoor, boiler in, boiler out, return, system) are resistance type. Compare readings to the sensor table.
Likely causes
- Sensor drifted or failed
- Wiring or connector fault
Check in this order
- Turn off power to the boiler.
- Measure sensor resistance with an ohmmeter at known temperatures: 32°F ice water, 60°F or 70°F room temperature, 212°F boiling water.
- Compare readings to the sensor resistance table (page 101).
- To check the control, connect a resistance decade box in place of a sensor and confirm the displayed temperature is close to the matching value.
Applies to: SVF 1500-3000 Series 1 boiler
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SVF Series 1 boiler manual, p. 100-101. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.