Weil-McLain · Boiler troubleshooting

Check temperature sensors

SVF Series 1

What is going on

Sensors (flue, outdoor, boiler in, boiler out, return, system) are resistance type. Compare readings to the sensor table.

Likely causes

  • Sensor drifted or failed
  • Wiring or connector fault

Check in this order

  1. Turn off power to the boiler.
  2. Measure sensor resistance with an ohmmeter at known temperatures: 32°F ice water, 60°F or 70°F room temperature, 212°F boiling water.
  3. Compare readings to the sensor resistance table (page 101).
  4. To check the control, connect a resistance decade box in place of a sensor and confirm the displayed temperature is close to the matching value.

Applies to: SVF 1500-3000 Series 1 boiler

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SVF Series 1 boiler manual, p. 100-101. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.