Set up 0-10 VDC remote target temperature control
What is going on
Uses a 0-10 VDC signal to set the supply target temperature instead of the outdoor sensor.
Check in this order
- Wire the 0-10 VDC signal to P15 pin 6 (positive) and pin 5 (common).
- Connect at least one dry contact heat demand to an unused input. Assign it to a priority in the Wizard or the contractor menu.
- On the priority used for heating (PRIORITY 2 for single boilers), set TARGET ADJUST to 0-10V.
- Set VOLTS FOR MAX to the voltage that calls for the highest target and set SUPPLY MAX to that temperature.
- Set VOLTS FOR MIN to the voltage that calls for the lowest target and set SUPPLY MIN to that temperature.
- Between the two voltages, the target scales linearly between SUPPLY MIN and SUPPLY MAX.
- Use PRIORITY 1 for DHW if it is used. Check that its values suit the application.
Applies to: SF-550 and SF-750 single boiler installations
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 3 boiler manual, p. 56. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.