Weil-McLain · Boiler troubleshooting

Set up 0-10 VDC remote target temperature control

SlimFit Series 3

What is going on

Uses a 0-10 VDC signal to set the supply target temperature instead of the outdoor sensor.

Check in this order

  1. Wire the 0-10 VDC signal to P15 pin 6 (positive) and pin 5 (common).
  2. Connect at least one dry contact heat demand to an unused input. Assign it to a priority in the Wizard or the contractor menu.
  3. On the priority used for heating (PRIORITY 2 for single boilers), set TARGET ADJUST to 0-10V.
  4. Set VOLTS FOR MAX to the voltage that calls for the highest target and set SUPPLY MAX to that temperature.
  5. Set VOLTS FOR MIN to the voltage that calls for the lowest target and set SUPPLY MIN to that temperature.
  6. Between the two voltages, the target scales linearly between SUPPLY MIN and SUPPLY MAX.
  7. Use PRIORITY 1 for DHW if it is used. Check that its values suit the application.

Applies to: SF-550 and SF-750 single boiler installations

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 3 boiler manual, p. 56. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.