Check the neutralization unit
What is going on
Checks condensate acidity and granulate level.
Check in this order
- Check condensate pH with a field-supplied pH strip.
- If pH is below 6.5, replace the granulate.
- If contaminated, rinse the neutralization unit with tap water.
- Refill the granulate up to the mark. The red marking is the minimum fill level.
Applies to: Vitodens 200-W B2HA 19, 28, 35
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 200-W B2HA service instructions, p. 24. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.