Viessmann · Boiler troubleshooting

Adjust the adjustable high limit to 100°C / 212°F

Vitotronic 300

What is going on

The adjustable high limit leaves the factory at 95°C. The adjustable range is 75 to 100°C / 167 to 212°F. Note the setting of coding address 06 before making changes.

Check in this order

  1. Using a suitable screwdriver, lever out and remove the selector knob R behind the hinged cover.
  2. Using pointed pliers, break off the cams in the shaded areas on the stop dial to limit the range to the desired value.
  3. Fit the selector knob R so that the marking is in the centre of the selected range.
  4. Note the setting of coding address 06.

Applies to: Adjustable high limit on Viessmann boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW2 installation and service instructions, p. 24. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.