Wire the CombiPLUS control and pump cables
What is going on
Route and connect the control cable and pump cable to the CombiPLUS, then to the boiler power pump module.
Check in this order
- Remove both standard knock-outs on the rear right side of the CombiPLUS A. Route the control cable through one and the pump cable through the other, then secure them with the locknuts.
- Connect the electrical connectors inside the CombiPLUS: pump, diverting valve motor, flow sensor and water temperature sensor.
- At the power pump module, route the control cable through the fourth hole in the base and the pump cable through the second hole, then secure them with locknuts.
- Connect pump cable wires black 1 (neutral) to X3 neutral, black 2 (line) to X3 line, and green/yellow ground to any open terminal on X2.
- Connect the five-pin DHW temperature sensor/flow sensor connector to X7 and the six-pin diverter valve connector to X10.
- Install the anchors and the conduit clip behind the cables, then press both cables into the clip.
Applies to: CombiPLUS A and Vitodens 100-W WB1B power pump module
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 100-W WB1B installation and service instructions, p. 29, p. 32. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.