Viessmann · Boiler troubleshooting

Check diaphragm expansion tank and system pressure

Vitodens 200-W B2HA

What is going on

Perform with the system cold.

Likely causes

  • Lower manometer reading usually means water loss from leakage

Check in this order

  1. Drain the boiler or system and reduce pressure until the manometer reads 0.
  2. If tank nitrogen pressure is below system static pressure, charge the membrane to slightly above system pressure.
  3. Top up with water until the fill pressure is about 3 psig above static pressure.
  4. On first start-up, mark this value as the minimum fill pressure on the manometer.
  5. Repair all leaks.

Applies to: Vitodens 200-W B2HA 19, 28, 35

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 200-W B2HA service instructions, p. 24. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.