Viessmann · Boiler troubleshooting
Check diaphragm expansion tank and system pressure
What is going on
Perform with the system cold.
Likely causes
- Lower manometer reading usually means water loss from leakage
Check in this order
- Drain the boiler or system and reduce pressure until the manometer reads 0.
- If tank nitrogen pressure is below system static pressure, charge the membrane to slightly above system pressure.
- Top up with water until the fill pressure is about 3 psig above static pressure.
- On first start-up, mark this value as the minimum fill pressure on the manometer.
- Repair all leaks.
Applies to: Vitodens 200-W B2HA 19, 28, 35
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 200-W B2HA service instructions, p. 24. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.