Replace combustion fan

Vitocrossal 300 CA3B

What is going on

Fan removal with the Venturi pipe and gas valve.

Check in this order

  1. Disconnect both fan connectors.
  2. Remove the 6 nuts on the Venturi pipe and remove the Venturi pipe with the fitted gas valve. Tighten to 4.5 lb.ft (6 Nm) on reassembly.
  3. Undo the hex nuts from the 4 studs.
  4. Remove the fan and note how the gasket sits.
  5. Install in reverse order. Fit the gasket in the correct position.

Applies to: CA3B 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Service Instructions, p. 65. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.