Viessmann · Boiler troubleshooting
Checking the electrical connect module fuses
What is going on
Check the fuses on the power/pump connection interface and on the Integrate EA1 module.
Likely causes
- Blown fuse F1 or F2 on the power/pump connection interface
- Blown fuse F1 or F2 on the Integrate EA1 module
Check in this order
- Switch off the power.
- Remove the front panel and cover (see page 93).
- Check fuse F1 and F2 of the power/pump connection interface (fuse F2 is the one labelled D, fuse F1 the one labelled E in the legend).
- Check fuse F1 and F2 of the Integrate EA1 module (fuse F1 is labelled C in the legend).
Applies to: Vitocrossal 300 CU3A 26 to 199
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 96. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.