Weil-McLain · Boiler troubleshooting

Check water system pressure and automatic air vents

SlimFit Series 3

What is going on

Confirm cold fill pressure and control pressure rise during heat-up.

Likely causes

  • Pressure that rises too far during heat-up points to an expansion tank sizing or performance problem.

Check in this order

  1. Confirm all system components are installed correctly and working.
  2. Check cold fill pressure. It is usually about 12 psig.
  3. Watch system pressure while the boiler heats up and confirm it does not rise too high.
  4. Inspect automatic air vents and air separators. Remove the vent caps and briefly press the push valve to flush each vent. Reinstall the caps.
  5. Replace any vent that leaks.
  6. Check water chemistry (inhibitor concentration, pH and hardness). See page 83.

Applies to: SlimFit 550 and 750 Series 3

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit series3 commercial gas-fired water boiler boiler manual, p. 92. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.