Weil-McLain · Boiler troubleshooting
Check water system pressure and automatic air vents
What is going on
Confirm cold fill pressure and control pressure rise during heat-up.
Likely causes
- Pressure that rises too far during heat-up points to an expansion tank sizing or performance problem.
Check in this order
- Confirm all system components are installed correctly and working.
- Check cold fill pressure. It is usually about 12 psig.
- Watch system pressure while the boiler heats up and confirm it does not rise too high.
- Inspect automatic air vents and air separators. Remove the vent caps and briefly press the push valve to flush each vent. Reinstall the caps.
- Replace any vent that leaks.
- Check water chemistry (inhibitor concentration, pH and hardness). See page 83.
Applies to: SlimFit 550 and 750 Series 3
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit series3 commercial gas-fired water boiler boiler manual, p. 92. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.