Cascade strategy: net calorific 1 (coding 3C: 1)

Vitocontrol-S VD2/CT3/CM2

What is going on

Conventional boilers run at their upper output range to prevent condensate from low return temperatures. Fewest boilers are active.

Check in this order

  1. Start-up the start-up integral must exceed the limit set in coding 45. The next boiler in the sequence then starts.
  2. Shutdown a boiler shuts down (coding 3d: 1) when the remaining boilers can meet the required output without the boiler started last.

Applies to: Vitocontrol-S VD2/CT3/CM2 cascade

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocontrol-S VD2/CT3/CM2 installation and service manual, p. 127. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.