Viessmann · Boiler troubleshooting
Check flue gas flapper
What is going on
Check the flue gas flapper and its gasket for dirt and damage.
Check in this order
- Undo the three screws and remove the fan.
- Remove the flue gas flapper.
- Check the flapper and gasket for dirt and damage. Replace as necessary.
- Refit the flue gas flapper.
- Refit the fan and secure with three screws. Torque to 2.2 lb.ft (3.0 Nm).
Applies to: Vitodens 200-W B2HB 45, 57, 160, 199
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HB service instructions, p. 24. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.