Viessmann · Boiler troubleshooting

Venting option #2 (Category III) requirements

Vitorond 200VD2

What is going on

The Vitorond 200 is a Category III positive pressure, non-condensing boiler and must be vented individually. The vent system and chimney must be designed for the boiler and must be gas tight. Use only the approved stainless venting listed for Category III.

Check in this order

  1. Vent each boiler individually; do not share the vent.
  2. Use AL29-4C stainless steel single-wall vertical venting that is UL/ULC listed for Category III.
  3. Confirm the chimney is gas tight before connecting.
  4. Size the chimney for the actual boiler model and input, not the flue outlet size.
  5. Follow the Viessmann positive pressure venting system instructions when using that option.

Applies to: Vitorond 200 VD2 320 to 1080 boilers, Category III venting

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 200 VD2 installation manual, p. 24. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.