Checking the CGa boiler out temperature sensor

Weil-McLain CGa Series 4

What is going on

How to test the outlet thermistor and the control's reading.

Likely causes

  • Sensor out of range
  • Damaged wiring
  • Control misreading

Check in this order

  1. Turn off power to the boiler before unplugging connectors or measuring resistance.
  2. Unplug the sensor and measure resistance with an ohmmeter.
  3. Easy reference points ice water (32°F) about 293,920-374,080 ohms; room temperature 68°F about 110,414-140,526 ohms; 77°F about 88,000-112,000 ohms; boiling water (212°F) about 5,605-7,133 ohms.
  4. Far outside the range for the temperature: replace the sensor.
  5. To check the control itself, put a resistance decade box in place of the sensor and see if the display shows the matching temperature.

Applies to: CGa-25 to CGa-8, natural gas (config #15) and propane (config #5)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain CGa Series 4 Boiler Manual 550-100-223/0425, Table 10 Sensor resistance values, p.63 (table text is jumbled in the export: check the values on the page). Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.