Weil-McLain · Boiler troubleshooting
Checking the CGa boiler out temperature sensor
What is going on
How to test the outlet thermistor and the control's reading.
Likely causes
- Sensor out of range
- Damaged wiring
- Control misreading
Check in this order
- Turn off power to the boiler before unplugging connectors or measuring resistance.
- Unplug the sensor and measure resistance with an ohmmeter.
- Easy reference points ice water (32°F) about 293,920-374,080 ohms; room temperature 68°F about 110,414-140,526 ohms; 77°F about 88,000-112,000 ohms; boiling water (212°F) about 5,605-7,133 ohms.
- Far outside the range for the temperature: replace the sensor.
- To check the control itself, put a resistance decade box in place of the sensor and see if the display shows the matching temperature.
Applies to: CGa-25 to CGa-8, natural gas (config #15) and propane (config #5)
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain CGa Series 4 Boiler Manual 550-100-223/0425, Table 10 Sensor resistance values, p.63 (table text is jumbled in the export: check the values on the page). Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.