Maintenance message comes back on Monday morning
What is going on
After a service, the maintenance message can return on the next Monday morning if coding 24 is not reset. This applies to both control units when the Vitocontrol-S is used.
Likely causes
- Coding 24 on Vitotronic 100 GC1 was not reset to 0 after maintenance.
Check in this order
- Set coding 24 to 1 and then back to 0 on the Vitotronic 100 GC1 if maintenance was done before the message appeared.
- After maintenance, set coding 24 to 0 on the Vitotronic 100 GC1.
- Acknowledge the maintenance display on both control units if required.
Applies to: Vitotronic 100 GC1 with Vitocontrol-S
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100 GC1 and Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 107. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.