Viessmann · Boiler troubleshooting
Opening the junction box and moving the control base to service position
What is going on
Access the wiring area of the control unit. Only needed when the programming unit is at the bottom.
Check in this order
- Discharge static by touching grounded metal such as a water pipe before starting.
- Release the tabs on the boiler control base.
- Pull the control base straight out.
- Place the control base in the service position, aligning its rear positioning tabs with the holes in the boiler jacket, and lock with the control base clips.
- Do not unplug the cable from the mounting panel.
- Do not change the position of the cable or its strain relief on the boiler jacket.
- Release the junction box cover clamps.
- Lift the junction box cover.
Applies to: Vitodens 100-W B1HE/B1KE
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 100-W B1HE/B1KE installation manual, p. 25. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.