Weil-McLain · Boiler troubleshooting
No spark, system does not work (without vent damper, Chart 1)
What is going on
Troubleshooting chart for a no-spark condition on steam boilers without a vent damper. The flowchart text is out of order in the extracted pages, so the sequence below follows the chart's checks.
Likely causes
- Vent damper plug missing (with damper systems)
- Ground wiring faulty
- No 24 VAC at the ignition control
- Open thermostat, circulator relay, spill switch, rollout fuse, LWCO or limit contacts
- Spark wire, electrode or gap faulty
Check in this order
- Turn off supply voltage before checking connections.
- Check that the vent damper plug is in place. If not, replace the damper plug and retest.
- Visually check the ground wire from GND (Burner) to the ignition control mounting screw, and from transformer terminal C to case ground.
- Check for 24 VAC across terminals 24V and 24V(GND). If absent, check for an open thermostat, circulator relay, loose wires, defective spill switch or rollout thermal fuse, or open LWCO or limit contacts. If LWCO, spill switch or rollout contacts are open, find and correct the cause before continuing.
- Open the thermostat contacts for 15 seconds, then close them, and check for 24 VAC across PV and MV/PV.
- Check that the spark wire is securely connected to the spark transformer and is not cut, brittle, burned or cracked.
- Check that the spark electrode ceramic is not cracked.
- Check that the spark gap is 0.125 in and located in the pilot gas stream.
- If the wiring and parts check out, replace the pilot assembly or ignition control as indicated, turn on supply voltage, and run several complete heat cycles.
Applies to: EG and PEG steam boilers without vent damper
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: EG / PEG Series 7 Boiler Manual, p. 78. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.