Check temperature sensors (resistance method)

Ultra Series 4

What is going on

All boiler sensors (flue, outdoor, return water, supply water) are resistance type. Compare measured ohms with Figure 123.

Likely causes

  • Out-of-range sensor resistance
  • Wrong sensor reading on the display

Check in this order

  1. Measure sensor resistance at known temperatures: 32 °F (ice point), 60 °F, 70 °F and 212 °F (boiling point at sea level). For ice and boiling points, put the sensor in water at that temperature.
  2. Use an ohmmeter and compare with Figure 123 (page 116).
  3. To check the control, connect a resistance decade box in place of the sensor and confirm the U-Control temperature matches the resistance.

Applies to: Ultra 80, 105, 155, 230, 299, 399

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Ultra Series 4 gas-fired water boiler manual, p. 116. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.