Zone circuit setpoint: fixed or weather compensated

Vitocrossal 300 CU3A

What is going on

With one zone circuit, choose the zone set point method. Fixed setpoint: enter the target boiler water temperature used on a zone call. Weather compensated: adjust slope and shift to set the heating curve; the calculated set point is used while the zone demand lasts.

Check in this order

  1. Select the number of zone circuits matching the thermostats connected to the DE terminals.
  2. Choose Fixed Setpoint or Weather Compensated.
  3. For fixed setpoint, enter the target water temperature.
  4. For weather compensated, adjust slope and shift.
  5. Select the pump output to energize during a zone call (P3 on 28/20 in Application 1).
  6. Check the zone output summary and go back if it is incorrect.
  7. Finish start-up; the boiler is ready for operation.

Applies to: Vitocrossal 300 CU3A zone control, 1 zone circuit

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CU3A application guide, p. 24. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.