Viessmann · Boiler troubleshooting
Match control to a modulating burner
What is going on
Measure burner output range on a running burner and enter the values in coding 1. The burner must be adjusted first. Keep minimum output as low as the flue system allows.
Check in this order
- Start the burner.
- Press the menu and OK buttons together for about 2 seconds to start the relay test.
- Activate Burner mod. open and wait until the actuator reaches maximum output. Note the maximum output from fuel consumption.
- Activate Burner mod. closed and time how long the actuator takes to reach minimum output. Note that time in seconds.
- Note the minimum (basic) output from fuel consumption.
- Activate Burner mod. open again and stop the actuator after one third of the measured time. Note the partial output from fuel consumption.
- Press OK to end the relay test.
- Enter the values in coding 1 (see next setting).
Applies to: Vitotronic 300 GW2 with modulating burner
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300 GW2 installation and service instructions, p. 69-70. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.