Match control to a modulating burner

Vitotronic 300

What is going on

Measure burner output range on a running burner and enter the values in coding 1. The burner must be adjusted first. Keep minimum output as low as the flue system allows.

Check in this order

  1. Start the burner.
  2. Press the menu and OK buttons together for about 2 seconds to start the relay test.
  3. Activate Burner mod. open and wait until the actuator reaches maximum output. Note the maximum output from fuel consumption.
  4. Activate Burner mod. closed and time how long the actuator takes to reach minimum output. Note that time in seconds.
  5. Note the minimum (basic) output from fuel consumption.
  6. Activate Burner mod. open again and stop the actuator after one third of the measured time. Note the partial output from fuel consumption.
  7. Press OK to end the relay test.
  8. Enter the values in coding 1 (see next setting).

Applies to: Vitotronic 300 GW2 with modulating burner

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW2 installation and service instructions, p. 69-70. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.