Viessmann · Boiler troubleshooting
Check and clean ignition and ionization electrodes
What is going on
Check electrodes for wear and contamination, clean them and check the gaps.
Likely causes
- Wear or contamination on the electrodes
- Electrode gaps not as specified
- Damaged electrodes
Check in this order
- Check the ignition electrodes and ionization electrode for wear and contamination.
- Clean the electrodes with a small brush (not a wire brush) or emery paper.
- Check the electrode gaps. If the gaps are wrong or the electrodes are damaged, replace them and align them with new gaskets.
- Tighten the electrode fixing screws to 1.5 lb.ft (2 Nm) with a calibrated torque wrench.
Applies to: Vitodens 200-W B2HB 45, 57, 160, 199
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HB service instructions, p. 25. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.