Replace gas solenoid valve or BCU on a lag boiler
What is going on
On lag boilers the gas solenoid valve and the BCU cannot be replaced directly with the ViGuide app.
Check in this order
- Put the lag boiler into single boiler mode.
- Load the current parameters with the ViGuide app.
- Replace the gas solenoid valve or the burner control unit.
- Reincorporate the boiler into the cascade once the replacement is complete.
Applies to: Vitocrossal 200 CI2 lag boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CI2 Service Instructions, p. 79. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.