Glow Brand · Boiler troubleshooting
Plate heat exchanger (PHE) cleaning
What is going on
Removing and cleaning the domestic plate heat exchanger to remove calcium buildup. Clean regularly if the domestic water is not treated.
Likely causes
- Calcium buildup and narrowed passages from untreated domestic water
Check in this order
- Call for heat off, let the post-purge finish, turn gas off and remove power.
- Isolate and drain both the central heat loop and the domestic side.
- Swing the control panel out. Disconnect the fan, gas valve, ignition and ionization electrode cabling. Disconnect the gas supply pipe at the gas valve inlet union and discard the fiber washers.
- Once the chamber has cooled, remove the four nuts holding the burner assembly. Lift out the assembly and protect the refractory disc. Replace the refractory if damaged.
- Remove the two flanged front screws on the CHB with a 4 mm or 5/32 in Allen wrench, holding the PHE in place. Lift the PHE out without getting water on components.
- Check the four PHE sealing gaskets for wear and replace as needed.
- Clean the PHE with a suitable commercial descaler or vinegar.
- Flush the PHE thoroughly with clean water.
- Fit new gaskets.
- Reinstall the PHE behind the CHB and tighten the two screws.
- Reassemble in reverse order using new fiber washers on the gas pipe.
- Return water pressure and purge all air from the central heat side.
- Open the domestic outlet drain or a nearby hot tap and flush the PHE for 1 minute.
- Close the water flow and power on the boiler.
Applies to: C95 & C140
More boiler guides
Related
Glow Brand error codes · Glow Brand parts · Glow Brand tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Glow Brand C95 & C140 Installation & Operating manual, p. 82. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.