Viessmann · Boiler troubleshooting

Connect a return mixing valve or modulating valve actuator (CM2 only)

Vitotronic 100 GC1Vitocontrol-S VD2/CT3/CM2

What is going on

Wire a 120 V or 24 V valve actuator through a valve adaptor on the DIN rail inside the connection enclosure.

Check in this order

  1. Disconnect power to the control.
  2. Mount the 120 V or 24 V valve adaptor on the DIN rail inside the connection enclosure.
  3. Plug the gS plug into the gS socket on the control.
  4. Secure the cable with a tie (see page 45).
  5. Connect the adaptor's black wire to the 120 V L out terminal on the DIN rail (terminals 10, 11 or 12).
  6. Wire the valve actuator leads to the adaptor terminals as shown in the figures.

Applies to: CM2 only, return mixing valve or isolation/modulating valve actuator

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 48. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.