Select a DHW circulator for direct-connected piping
What is going on
Add the boiler pressure drop, the piping pressure drop and the water heater pressure drop to get the total head. Then pick a circulator that delivers the required flow at that head.
Check in this order
- Get the required boiler water flow rate (GPM) at 190 F and the water heater pressure drop at that flow (feet of water) from the heater data.
- Find the boiler model in the pressure drop figure and pick the first flow rate at or above the required flow.
- Read the boiler pressure drop (H1) and piping pressure drop (H2) from that row, using the copper pipe size listed.
- Add H1, H2 and H3 (water heater drop) to get the total head.
- Select a circulator that delivers the required GPM against the total head.
Applies to: Combined space heating and DHW systems with direct-connected DHW piping
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Ultra Series 4 boiler manual 550-100-440/1025, p. 56. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.