Select a DHW circulator for direct-connected piping

Ultra Series 4

What is going on

Add the boiler pressure drop, the piping pressure drop and the water heater pressure drop to get the total head. Then pick a circulator that delivers the required flow at that head.

Check in this order

  1. Get the required boiler water flow rate (GPM) at 190 F and the water heater pressure drop at that flow (feet of water) from the heater data.
  2. Find the boiler model in the pressure drop figure and pick the first flow rate at or above the required flow.
  3. Read the boiler pressure drop (H1) and piping pressure drop (H2) from that row, using the copper pipe size listed.
  4. Add H1, H2 and H3 (water heater drop) to get the total head.
  5. Select a circulator that delivers the required GPM against the total head.

Applies to: Combined space heating and DHW systems with direct-connected DHW piping

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Ultra Series 4 boiler manual 550-100-440/1025, p. 56. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.