Installing the Modbus RTU wiring

NFB700

What is going on

Field wiring of the Modbus RTU board to the building automation system (RS-485 network). Power off the boiler before opening it.

Check in this order

  1. Turn off the power supply to the boiler.
  2. Release the 4 latches on the upper sides of the boiler and remove the upper-front cover.
  3. Connect the 3-pin terminal block on the right side of the front panel to the RS-485 device: A = RS-485 +, B = RS-485 -, G = RS-485 GND.
  4. If the RS-485 device needs power, wire it to the AC24VN and AC24VL ports of terminal block CNIN9 (the controller supplies 24VAC).
  5. For a BACnet or LonWorks gateway, follow the BACnet or LonWorks installation manual instead.
  6. In cascade systems, connect the RS-485 device to the front panel of the main unit.

Applies to: NFB700-500C/600C/800C/1000C

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien Modbus RTU installation & operation manual, p. 3. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.