Navien · Boiler troubleshooting
Installing the Modbus RTU wiring
What is going on
Field wiring of the Modbus RTU board to the building automation system (RS-485 network). Power off the boiler before opening it.
Check in this order
- Turn off the power supply to the boiler.
- Release the 4 latches on the upper sides of the boiler and remove the upper-front cover.
- Connect the 3-pin terminal block on the right side of the front panel to the RS-485 device: A = RS-485 +, B = RS-485 -, G = RS-485 GND.
- If the RS-485 device needs power, wire it to the AC24VN and AC24VL ports of terminal block CNIN9 (the controller supplies 24VAC).
- For a BACnet or LonWorks gateway, follow the BACnet or LonWorks installation manual instead.
- In cascade systems, connect the RS-485 device to the front panel of the main unit.
Applies to: NFB700-500C/600C/800C/1000C
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien Modbus RTU installation & operation manual, p. 3. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.