Burner connection with plug-in cables (CM2)

Vitotronic 100

What is going on

The burner cables come with the Vitotronic. Terminal codes: L1 is phase via the fixed high limit to the burner; N is neutral to the burner; T1 and T2 are the control circuit; S3 is for the burner fault indicator; B4 is for the burner hours counter. Terminals 1, 2 and 3 are the control circuit for a 2nd stage burner or modulation controller: 1 is from the burner, 2 is modulating down, 3 is modulating up or 2nd stage ON. Colour codes: BK black, BN brown, BU blue.

Check in this order

  1. Disconnect power to the burner and the boiler control.
  2. Connect the plug for the boiler control to the matching counter plug in the boiler control unit.
  3. Connect the 7-pole plug and the 3-pole plug to the burner.
  4. Connect the burner in accordance with applicable codes.

Applies to: CM2 burners with plug-in connection

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 GC1 installation and service instructions, p. 83. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.