Viessmann · Boiler troubleshooting
Burner connection with plug-in cables (CM2)
What is going on
The burner cables come with the Vitotronic. Terminal codes: L1 is phase via the fixed high limit to the burner; N is neutral to the burner; T1 and T2 are the control circuit; S3 is for the burner fault indicator; B4 is for the burner hours counter. Terminals 1, 2 and 3 are the control circuit for a 2nd stage burner or modulation controller: 1 is from the burner, 2 is modulating down, 3 is modulating up or 2nd stage ON. Colour codes: BK black, BN brown, BU blue.
Check in this order
- Disconnect power to the burner and the boiler control.
- Connect the plug for the boiler control to the matching counter plug in the boiler control unit.
- Connect the 7-pole plug and the 3-pole plug to the burner.
- Connect the burner in accordance with applicable codes.
Applies to: CM2 burners with plug-in connection
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100 GC1 installation and service instructions, p. 83. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.