Weil-McLain · Boiler troubleshooting

Six-month relief valve operation test

Ultra Series 4

What is going on

Lift the relief valve lever to check that it flows and reseats without weeping. Pipe the discharge to a safe place before testing.

Likely causes

  • Valve weeps after being lifted
  • Valve or discharge line blocked
  • Valve seat dirty

Check in this order

  1. Verify the relief valve outlet is piped to a safe discharge location that avoids scalding.
  2. Confirm the discharge line is metal and runs to a safe disposal point, as installed per the Ultra boiler manual.
  3. Read the pressure/temperature gauge to confirm the system is pressurized.
  4. Lift the relief valve top lever slightly so water flows through the valve and discharge piping.
  5. If water flows freely, release the lever and let the valve seat.
  6. Watch the discharge pipe end after it drains. If the valve weeps, lift the lever again to clean the seat.
  7. If the valve still weeps, call a qualified service technician to inspect the valve and system.
  8. If no water flows when the lever is fully lifted, shut the boiler down following page 9 and call a qualified service technician to check for a blocked valve or discharge line.

Applies to: Ultra Series 4 boiler relief valve and discharge line

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Ultra Series 4 user's information manual, p. 8. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.