Weil-McLain · Boiler troubleshooting
Six-month relief valve operation test
What is going on
Lift the relief valve lever to check that it flows and reseats without weeping. Pipe the discharge to a safe place before testing.
Likely causes
- Valve weeps after being lifted
- Valve or discharge line blocked
- Valve seat dirty
Check in this order
- Verify the relief valve outlet is piped to a safe discharge location that avoids scalding.
- Confirm the discharge line is metal and runs to a safe disposal point, as installed per the Ultra boiler manual.
- Read the pressure/temperature gauge to confirm the system is pressurized.
- Lift the relief valve top lever slightly so water flows through the valve and discharge piping.
- If water flows freely, release the lever and let the valve seat.
- Watch the discharge pipe end after it drains. If the valve weeps, lift the lever again to clean the seat.
- If the valve still weeps, call a qualified service technician to inspect the valve and system.
- If no water flows when the lever is fully lifted, shut the boiler down following page 9 and call a qualified service technician to check for a blocked valve or discharge line.
Applies to: Ultra Series 4 boiler relief valve and discharge line
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Ultra Series 4 user's information manual, p. 8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.