Viessmann · Boiler troubleshooting
Checking the mixing valve motor rotation direction
What is going on
After power-up the boiler runs a self-test that opens and closes the mixing valve. The supply temperature sensor should read a higher temperature when the valve opens. If the temperature drops, the motor turns the wrong way or the valve set is fitted incorrectly.
Likely causes
- Motor turning in the wrong direction
- Mixing valve set incorrectly fitted
Check in this order
- Let the boiler complete its self-test.
- Set the mixing valve manually to Open.
- Check that the supply temperature sensor reads a higher temperature.
Applies to: Vitodens 222-F B2TB extension kit
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 222-F B2TB service instructions, p. 87. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.