Navien · Boiler troubleshooting
Check CO2 at high fire and verify gas orifice
What is going on
Verify CO2 at high fire. If it does not match the table, do not change the gas valve. Check the gas orifice instead.
Likely causes
- CO2 at high fire does not match Table 2
- Incorrect gas orifice installed
Check in this order
- Open several DHW fixtures on full hot.
- Set the boiler to 2-stage D. MAX mode (see 12.6.7 Setting the Special Operation Modes).
- Measure CO2 at high fire.
- Compare the reading to Table 2.
- If CO2 does not match, do not adjust the gas valve. Check for the proper gas orifice.
Applies to: NCB700 boilers during gas conversion or commissioning
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NCB700 installation and operation manual, p. 144. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.