Weil-McLain · Boiler troubleshooting

Pilot lights but does not energize main gas valve(s)

CGi Series 5

What is going on

Pilot is burning but the control does not open the main gas valves.

Likely causes

  • Weak pilot flame signal
  • Flame rod corroded or wiring open
  • Pilot gas pressure too low at lower inlet pressures

Check in this order

  1. Check the pilot flame signal in control diagnostics. A signal below 60 is needed for a proven pilot.
  2. For burner ignition the flame signal must be below 25. If there is no signal or it is above 25, check the pilot flame sense wiring and flame rod for continuity and corrosion. Replace the rod if needed.
  3. If a pilot gas pressure regulator is used with low inlet pressure, raise the regulator setting to give the pilot more gas.

Applies to: CGi-25 to CGi-8

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: CGi Series 5 boiler manual, p. 77. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.