Weil-McLain · Boiler troubleshooting

Zone valve zoning, primary/secondary piping

SVF 500/600 Series 1

What is going on

Boiler loop is a secondary circuit off a primary system loop. This keeps sufficient flow in the boiler loop and keeps the boiler circulator head off the zone valves. A flow/check valve on the boiler outlet stops gravity circulation in the boiler loop during DHW heating.

Check in this order

  1. Install a system circulator (by installer) that delivers the required flow and head.
  2. Install the flow/check valve on the boiler outlet piping.
  3. Keep primary/secondary connection tees no more than eight pipe diameters apart.
  4. Place system supply and return sensors at least six pipe diameters, and no more than 3 ft, from the boiler connection tees.
  5. Use a strainer and a bypass pressure regulator where high-head pumps need one to protect control valves.

Applies to: Zone valve systems with boiler loop off a primary loop

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF 500/600 Series 1 boiler manual, pp. 24-25. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.