Zone valve zoning, primary/secondary piping
What is going on
Boiler loop is a secondary circuit off a primary system loop. This keeps sufficient flow in the boiler loop and keeps the boiler circulator head off the zone valves. A flow/check valve on the boiler outlet stops gravity circulation in the boiler loop during DHW heating.
Check in this order
- Install a system circulator (by installer) that delivers the required flow and head.
- Install the flow/check valve on the boiler outlet piping.
- Keep primary/secondary connection tees no more than eight pipe diameters apart.
- Place system supply and return sensors at least six pipe diameters, and no more than 3 ft, from the boiler connection tees.
- Use a strainer and a bypass pressure regulator where high-head pumps need one to protect control valves.
Applies to: Zone valve systems with boiler loop off a primary loop
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF 500/600 Series 1 boiler manual, pp. 24-25. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.