Viessmann · Boiler troubleshooting

Frost protection and central control

Vitocrossal 300 CA3B Dual Fuel

What is going on

Frost protection keeps the supply on the heating curve for the reduced room temperature but never below 50°F (10°C). Central control with coding 7a applies one heating circuit's operating and holiday program to the other circuits.

Check in this order

  1. For a variable frost limit, set coding a3 in the Heating circuit group.
  2. To enable central control, set coding 7a in the General group.
  3. Note that holiday programs on the other circuits are deleted when central control is enabled.
  4. Note that party and economy modes cannot be enabled on all control units.

Applies to: Heating circuits on CA3B Dual Fuel

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 Dual Fuel Service Instructions, p. 40. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.