Viessmann · Boiler troubleshooting

Control and junction box installation (CM2)

Vitotronic 300 GW2

What is going on

Capillaries and cables must not touch hot metal parts. Do not bend or kink the capillaries, because damaged capillaries cause malfunction. The ground screw and ground wire can be removed and refitted with the boiler back panel in place.

Likely causes

  • Bent or kinked capillaries
  • Cables touching hot metal components

Check in this order

  1. Route cables and capillaries from the control through the opening in the control panel, then through the rear panel opening and along the top rail to the control.
  2. Secure all cables to the rail with cable ties.
  3. Insert the capillaries into the sensor well.
  4. Mount the control to the control panel with the screws supplied in the boiler jacketing package.
  5. Install the junction box to the right or left of the rear panel and secure it with four 4 x 4.8 metal screws.

Applies to: Vitotronic 300 GW2 with CM2 control

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitotronic 300 GW2 installation and service instructions, p. 60. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.