Rinnai · Boiler troubleshooting

Wire the condensate pump safety switch

I-Series Plus

What is going on

Wires the pump's normally open contacts into the boiler so the boiler shuts down if the pump fails. Wiring must follow local codes and NEC.

Check in this order

  1. Disconnect power to the boiler.
  2. Open the boiler cover and find the two white wires marked To Condensate Pump. They may sit behind the PC board.
  3. Cut off the crimp connectors and strip both wire ends.
  4. Use wire rated 18 AWG or larger, strip both ends, and connect with wire nuts or approved connectors to the normally open contacts on the pump.
  5. Reconnect power and press the On/Off button on the controller.

Applies to: I-Series Plus condensing combi boilers with a condensate pump

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai I-Series Plus IP060160C installation manual, p. 65. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.