Viessmann · Boiler troubleshooting

Set CO2 at lower heating output

Vitocrossal 300 CA3B

What is going on

Adjust CO2 at partial load after setting full load.

Check in this order

  1. Press the button until the service indicator drops to 0 (lower heating output).
  2. Measure CO2 at the flue gas pipe.
  3. If CO2 must change, unscrew cover cap B.
  4. Turn adjusting screw A in small steps with a Torx 40. Clockwise raises CO2. Counter-clockwise lowers CO2.
  5. Record the reading in the maintenance record on page 162.
  6. Start the upper and lower outputs again from the control unit and recheck both values.
  7. Press the two buttons shown as S E and D together for more than 2 seconds to return the burner to operating mode.

Applies to: CA3B 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Service Instructions, p. 68. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.