Viessmann · Boiler troubleshooting
Set CO2 at lower heating output
What is going on
Adjust CO2 at partial load after setting full load.
Check in this order
- Press the button until the service indicator drops to 0 (lower heating output).
- Measure CO2 at the flue gas pipe.
- If CO2 must change, unscrew cover cap B.
- Turn adjusting screw A in small steps with a Torx 40. Clockwise raises CO2. Counter-clockwise lowers CO2.
- Record the reading in the maintenance record on page 162.
- Start the upper and lower outputs again from the control unit and recheck both values.
- Press the two buttons shown as S E and D together for more than 2 seconds to return the burner to operating mode.
Applies to: CA3B 2.5 to 6.0
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Service Instructions, p. 68. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.