Field wiring: power, circulator and strain relief
What is going on
Turn off power at the service panel before wiring. Use N.E.C. Class 1 wiring and type 105 C wire if replacing original wiring. Bond and ground the boiler per code. Use strain relief at the cabinet knockouts. The 24 V transformer output must not power external devices that are not listed in the manual. The boiler circulator relay on the expansion module is dry contact rated 10 A and needs external 120 VAC supply for the pump.
Check in this order
- Turn off electrical power at the service entrance panel.
- Feed line and low-voltage wiring through the top cabinet knockouts and install strain relief.
- Connect 120 VAC power to the boiler.
- Provide external 120 VAC power for the boiler circulator and wire it through the EP7 terminal, interrupting the pump's hot line.
- Confirm the circulator load is within the 10 A relay rating.
- Do not connect external devices to the 24 V transformer output unless listed in the manual.
- Ground and bond the boiler per code.
Applies to: SlimFit SF1000, SF1500, SF2000 field wiring
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SlimFit Series 2 boiler manual, p. 47. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.