Weil-McLain · Boiler troubleshooting

High altitude adjustment

ECO Tec Series 3

What is going on

Derate rules and CO2 adjustment at altitude.

Check in this order

  1. Set the correct altitude in the boiler setup menu; the control adjusts low, ignition and high fire rates.
  2. At 2500 ft and above, adjust CO2 manually per the gas valve procedure on p. 135.
  3. Use the CO2 settings for your gas type and altitude in Figure 128, p. 148.
  4. In the USA, input rates are derated 4% per 1,000 ft above sea level beyond 2,000 ft.
  5. In Canada, input is derated 10% for 2,000 to 4,500 ft; above 4,500 ft follow provincial authority and local codes.
  6. Above 11,000 ft, contact WM Technologies Technical Support.

Applies to: ECO Tec Series 3 gas boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec series 3 boiler manual, p. 143. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.