Weil-McLain · Boiler troubleshooting
High altitude adjustment
What is going on
Derate rules and CO2 adjustment at altitude.
Check in this order
- Set the correct altitude in the boiler setup menu; the control adjusts low, ignition and high fire rates.
- At 2500 ft and above, adjust CO2 manually per the gas valve procedure on p. 135.
- Use the CO2 settings for your gas type and altitude in Figure 128, p. 148.
- In the USA, input rates are derated 4% per 1,000 ft above sea level beyond 2,000 ft.
- In Canada, input is derated 10% for 2,000 to 4,500 ft; above 4,500 ft follow provincial authority and local codes.
- Above 11,000 ft, contact WM Technologies Technical Support.
Applies to: ECO Tec Series 3 gas boilers
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec series 3 boiler manual, p. 143. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.