Weil-McLain · Boiler troubleshooting

Zoning with circulators: four space heating zones (no indirect DHW)

SVF 500/600 Series 1

What is going on

Four thermostat-driven heating zones, each run by its own circulator from one boiler control. No indirect DHW on this layout.

Check in this order

  1. Review the boiler terminal wiring in Sections B and C (pages 72 and 73) before wiring.
  2. Wire zone thermostats to Inputs 1 to 4 (J17-1/2, J17-4/5, J17-7/8, J16-1/2).
  3. Wire circulators to outputs J4-1 to J4-4, each rated 2.2 A max, using BK, W and G conductors.
  4. Choose the space heating system type that matches the heating system during the Wizard setup, or set PRIORITY 2 manually in the System Settings menu.
  5. Keep the factory default settings for the chosen system type, or change them only if the system needs it.

Applies to: SVF 500/600 boilers, four zone circulator layout

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF 500/600 Series 1 boiler manual, p. 80. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.