Zoning with circulators: four space heating zones (no indirect DHW)
What is going on
Four thermostat-driven heating zones, each run by its own circulator from one boiler control. No indirect DHW on this layout.
Check in this order
- Review the boiler terminal wiring in Sections B and C (pages 72 and 73) before wiring.
- Wire zone thermostats to Inputs 1 to 4 (J17-1/2, J17-4/5, J17-7/8, J16-1/2).
- Wire circulators to outputs J4-1 to J4-4, each rated 2.2 A max, using BK, W and G conductors.
- Choose the space heating system type that matches the heating system during the Wizard setup, or set PRIORITY 2 manually in the System Settings menu.
- Keep the factory default settings for the chosen system type, or change them only if the system needs it.
Applies to: SVF 500/600 boilers, four zone circulator layout
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF 500/600 Series 1 boiler manual, p. 80. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.