Viessmann · Boiler troubleshooting
Frost protection function
What is going on
Frost protection applies to all heating programs and runs on the outdoor temperature.
Check in this order
- Expect frost protection to start when the outdoor temperature drops below about 34 °F (1 °C).
- Expect the heating circuit pump to run and the boiler water to be held near 68 °F (20 °C).
- Expect the DHW tank to be heated to about 68 °F (20 °C).
- Expect frost protection to stop when outdoor temperature rises above about 37 °F (3 °C) with default settings.
Applies to: Heating system freeze protection
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 200-W B2HB technical data manual, p. 23. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.