Viessmann · Boiler troubleshooting
Check coaxial venting for leaks
What is going on
Simplified leak test by measuring CO2 or O2 in the combustion air in the coaxial gap of the air intake pipe.
Check in this order
- Measure CO2 in the combustion air in the coaxial gap of the air intake pipe.
- Vent pipe is acceptable if CO2 is no higher than 0.2% or O2 is no lower than 20.6%.
- If CO2 is higher or O2 is lower, check the venting system thoroughly.
- Use the two measurement ports on the vent pipe adaptor: one for combustion air intake and one for flue gas.
Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA 80 to 100, 285 to 352 service instructions, p. 23. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.