Viessmann · Boiler troubleshooting

Check the boiler temperature sensor

Vitotronic 100 GC1

What is going on

Test the boiler water sensor against the actual water temperature.

Check in this order

  1. Disconnect power to the control and the burner.
  2. Unplug the boiler temperature sensor in the terminal compartment.
  3. Measure resistance between terminals 1 and 2 (or 2 and 3 if a second DHW sensor is connected).
  4. Compare the reading with the resistance table for the measured water temperature.
  5. If the value differs significantly, check the installation and replace the sensor if needed.

Applies to: Boiler temperature sensor

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 GC1 installation and service instructions, p. 50. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.